Double Check Valve Assembly (DCVA)
The standard moderate-hazard backflow preventer for commercial properties. Two independently operating check valves provide redundant protection against backpressure and back-siphonage from non-health-threatening connections.
Technical Specification
- CSA Standard
CSA B64.5— Double Check Valve Assemblies- Also listed as
- ASSE 1015 (US)
- Protection Level
- Moderate — protects against both backpressure and back-siphonage
- Hazard Classification
- Moderate-hazard (non-health-threatening) connections
- Testing Frequency
- Annual
- Installation
- May be installed below grade or in a vault; no relief valve discharge to accommodate
CSA B64.5 — Canadian Standards Association; ASSE 1015 — American Society of Sanitary Engineering
How the DCVA Works
The DCVA contains two independently operating spring-loaded check valves in series. Each check valve opens under normal supply pressure and closes if downstream pressure equals or exceeds supply pressure (backpressure condition) or if supply pressure drops below atmospheric (back-siphonage condition).
Because the two check valves operate independently, both would have to fail simultaneously for backflow to occur — providing meaningful redundancy for moderate-hazard applications. Unlike the RPZ, the DCVA does not have a relief valve and therefore cannot protect against severe-hazard connections where both check valves failing simultaneously would represent an unacceptable risk.
Check valve components degrade silently over time. A DCVA that shows no external sign of failure may have check valves that no longer hold the required differential pressure. Annual field testing with a calibrated gauge is the only way to confirm that each check valve remains functional.
Required Applications
- Multi-unit residential buildings (5+ units) — Main service connection; system water presents a moderate cross-connection hazard
- Office buildings — Standard commercial water service connections
- Retail commercial properties — Non-food-service commercial water service connections
- Fire suppression systems (without antifreeze or additives) — Fire system water that has been in the system is non-health-hazard; DCVA or DCDA used
- Hotels (service connection only) — Where commercial kitchen and severe-hazard connections are separately protected
- Light industrial without chemical connections
Note: If a building has mixed uses where one connection requires an RPZ, the water authority may require the entire main service connection to be protected by an RPZ rather than a DCVA.
Testing Procedure
DCVA testing verifies that each check valve holds under the specified pressure differential. The tester connects a differential pressure gauge to the test cocks and performs a differential pressure test on each check valve individually. A passing test requires:
- Check valve #1: opens at supply pressure; holds at specified minimum differential (typically 1 psi / 7 kPa)
- Check valve #2: opens at supply pressure; holds at specified minimum differential
- Both shut-off valves are operational
DCVA vs. DCDA
A Double Check Detector Assembly (DCDA) — also called a Double Check Valve Detector Assembly — is used specifically for fire sprinkler system connections. It adds a bypass line with a small meter to detect leakage or unauthorized water use through the fire system. The backflow prevention mechanism is the same as the DCVA.
Frequently Asked Questions — DCVA
Can a DCVA be installed underground?
Yes. Unlike RPZ assemblies, DCVAs can be installed below grade in a vault or pit because they do not have a relief valve that discharges water. The installation must still be accessible for testing and must not be subject to flooding (which could introduce contaminants). Water authorities may have specific vault installation requirements.
Does my multi-unit residential building need a DCVA or an RPZ?
Most multi-unit residential buildings are assigned a DCVA on the main service connection because the hazard — system water that has been in the building's plumbing — is classified as moderate. However, if the building has amenities like a swimming pool, laundry room with chemical dispensing, or food service, those connections may require separate RPZ protection. The water authority makes the classification.
What is the difference between a DCVA and an RPZ?
Both prevent backflow, but the RPZ provides a higher level of protection through its pressure differential relief valve. If the first check valve of an RPZ fails, the relief valve opens and discharges rather than allowing backflow. A DCVA relies solely on two check valves. Water authorities require RPZ assemblies for severe-hazard connections and DCVAs for moderate-hazard connections.