Technical Specification

CSA Standard
CSA B64.4 — Reduced Pressure Principle Backflow Preventers
Also listed as
ASSE 1013 (US); USC FCCCHR (Foundation for Cross-Connection Control)
Protection Level
Highest — protects against both backpressure and back-siphonage
Hazard Classification
Severe-hazard connections
Testing Standard
Field test per manufacturer procedure with calibrated differential pressure gauge; results reported to water authority
Testing Frequency
Annual minimum; more frequently if the water authority requires or after repair
Installation Requirement
Must be installed above grade, accessible, with full-bore shut-off valves and test cocks

CSA B64.4 — Canadian Standards Association; ASSE 1013 — American Society of Sanitary Engineering


How the RPZ Works

The RPZ assembly contains three key components operating in series:

  1. First check valve — Spring-loaded; closes to prevent backflow from the downstream side
  2. Reduced pressure zone (middle zone) — A hydraulically isolated zone maintained at a pressure lower than the supply pressure by at least 2 psi (14 kPa)
  3. Relief valve — Mechanically independent; opens and discharges to atmosphere if the pressure in the zone rises to within 2 psi of supply pressure (indicating check valve failure), preventing contaminated water from reaching the supply
  4. Second check valve — Downstream spring-loaded check valve providing an additional barrier

The relief valve is the critical safety feature. If the first check valve fails while the second check valve holds, the relief valve will open and discharge rather than allow backflow. If the relief valve is discharging continuously during normal operation, this indicates a failed first check valve and the assembly requires immediate service.


Required Applications

Water authorities require RPZ assemblies for any connection classified as severe-hazard, where the substance connected to the water system could cause illness, injury, or death if it contaminated the potable supply. Common commercial applications include:

  • Medical and dental offices — Autoclaves, sterilizers, dental chair water lines, procedure room equipment
  • Restaurants and food service — Carbonated beverage dispensers (CO₂ connections), commercial dishwashers, pre-rinse stations
  • Industrial / manufacturing — Process water connections, chemical storage connections, cooling towers with biocide treatment, boiler feed with chemical additives
  • Car washes — Detergent and chemical injection systems
  • Irrigation systems with chemical injection — Fertilizer, herbicide, or pesticide injection elevates irrigation from minor to severe hazard
  • Healthcare facilities — Laboratory water connections, medical gas systems
  • Funeral homes — Embalming room connections
  • Veterinary clinics — Surgical suite and grooming water connections

Annual Testing Procedure

RPZ assemblies are tested using a calibrated differential pressure test gauge connected to the test cocks installed on the assembly. The test verifies:

  • Both check valves are seated properly and not leaking
  • The relief valve opens at the correct differential (typically 2 psi / 14 kPa or greater difference between supply and zone pressure)
  • The relief valve closes tightly when the differential is restored
  • The shut-off valves are operational

A passed test is documented with specific pressure readings for each check valve and the relief valve opening differential. This documentation is submitted to the governing water authority and provided to the property owner.

Check valve seats, disc assemblies, and O-rings degrade over time with no visible external sign. An assembly that looks intact and has not been disturbed may no longer hold the required differential pressure — a condition undetectable without a field test. Annual testing with a calibrated gauge is the only reliable method to confirm that internal components remain functional between inspection cycles.


Common Failure Modes

FailureSymptomAction Required
First check valve fails closed / leakingLow differential across first check; relief valve dischargesRepair or replace first check module
Second check valve failsLow differential across second checkRepair or replace second check module
Relief valve fails to openRelief differential test fails — won't open at required thresholdReplace relief valve module
Relief valve fails to close (leaking)Continuous dripping from relief valve during normal supply conditionsClean seat or replace relief valve module
Debris foulingErratic test readings; relief valve cyclingDisassemble, clean, inspect seats and discs

Frequently Asked Questions — RPZ Assembly

What is a Reduced Pressure Zone (RPZ) assembly?

A Reduced Pressure Zone assembly is a high-protection backflow preventer consisting of two independently operating spring-loaded check valves with a hydraulically operated, mechanically independent pressure differential relief valve located in the zone between the two check valves. It is listed under ASSE 1013 and is required for severe-hazard cross-connection control applications.

When is an RPZ assembly required instead of a DCVA?

Water authorities require an RPZ when the connection presents a severe cross-connection hazard — where contaminants could cause illness or injury if they entered the potable supply. DCVAs are used for moderate-hazard connections where non-health-threatening substances (like system water in a multi-unit residential building) present the risk. The authority makes the hazard classification decision.

Can an RPZ assembly be installed indoors?

Yes, but the relief valve discharges water when activated, so indoor installations require a drain connection capable of handling the full flow of the assembly. Floor drains must not be connected to the sanitary system in a way that would create a cross-connection at the drain. Many water authorities have specific installation requirements for indoor RPZ assemblies.

How often does an RPZ need to be tested?

Annual testing is the minimum required by all Canadian municipal water authorities. RPZ assemblies should also be tested after any repair, after any backflow event or suspected contamination, and after the assembly has been shut off and drained (as this can displace debris).

Need your RPZ assembly tested?

Same-day compliance certificates across Canada.

Find Your City Request a Quote